Skip to product information
1 of 1
Shamrock Controls div. of Burns Controls Company →

2-Pole Definite Purpose Contactor - 30A, 277V Coil Voltage

2-Pole Definite Purpose Contactor - 30A, 277V Coil Voltage

SKU:DPC-409f19

Reliable 2-Pole Contactor for motors, lighting, HVAC fans. 30A, 277V. Industry-standard compliant.

Regular price $45.99
Regular price Sale price $45.99
Sale

Initiate Order

2-Pole Definite Purpose Contactor - 30A, 277V Coil Voltage

2-Pole Definite Purpose Contactor - 30A, 277V Coil Voltage

$45.99

Quantity: 1

Claim Your Seller Account

2-Pole Definite Purpose Contactor - 30A, 277V Coil Voltage

2-Pole Definite Purpose Contactor - 30A, 277V Coil Voltage

$45.99

Quantity: 1

Delivery via Maden

Expect your order to arrive on time.

Secure Payments

All orders are processed through a secure, PCI-compliant checkout.

View full details
The 2-Pole Definite Purpose Contactor is designed for precise control of motors, power supplies, lighting, HVAC fans, and compressors. With a resistive rating current of 30A, coil voltage of 277V, and a durable build with specifications meeting industry standards, this contactor ensures reliable functionality in various environments.

Product Specifications

Coil Data Coil Voltage
277 V
Coil Data Duty Cycle
Continuous
Coil Data Frequency
50 Hz | 60 Hz
Coil Data Minimum Initial Insulation Resistance
100 MΩ
Coil Data Normal Inrush Apparent Power
65 V·A
Coil Data Sealed Apparent Power
7.5 V·A
Environment Ambient Air Dampness Around The Device Relative Humi
45 to 85 %
Environment Ambient Air Temperature
40 to 65 ºC
Environment Coil Apply Voltage At 5060 Hertz Hz Frequency
75 to 110 %
Environment Maximum Operating Altitude Above Sea Level
2000 m
Environment Operating Temperature
-5 to 55 ºC
Specifications Locked Rotor Per Pole Current At 240 Alternating
120 A
Specifications Number Of Poles
2
Technical Data Full Load Expected Life
200000 Operations
Technical Data Full Load Inductive Current
20 A
Technical Data Locked Rotor Per Pole Current At 480 Alternating
100 A
Technical Data Locked Rotor Per Pole Current At 600 Alternating
80 A
Technical Data Mechanical Alternating Current Ac Coil Operations
2 Million
Technical Data Minimum Contact Data At 120 Alternating Current V
3 A
Technical Data Resistive Rating Current
30 A