The 32 Ampere T-Range 3 Pole Contactor is a reliable solution for high-power electrical applications. With a maximum inductive AC current of 22A, this contactor ensures efficient power distribution and control. It complies with a range of international standards such as BSEN60947, IEC60947, UL, and CSA approvals, guaranteeing safety and quality. Its compact design and versatile auxiliary contacts make it suitable for various industrial settings.
Product Specifications
Control Circuit Characteristics Average Consumption At 20 Degree
0.3 V·A
Control Circuit Characteristics Average Operating Time At Rated
4 to 12 ms
Control Circuit Characteristics Mechanical Life Rated Control Ci
15 cycles
Control Circuit Characteristics Operational Control Voltage For
0.8 to 1.1 Uc
Control Circuit Characteristics Rated Control Circuit Voltage Uc
12 to 660 V
Dimensions Depth D
85 mm
Dimensions Dimension C
85 mm
Dimensions Dimension D Lacdk1
138 mm
Dimensions Dimension D Ta1
118 mm
Dimensions Dimension D Ta2ta3
125 mm
Dimensions Dimension G
35 mm
Dimensions Height H
74 mm
Dimensions Minimum Electrical Clearance D
10 mm
Dimensions Width W
45 mm
Integral Auxillary Contact Characteristics Rated Operational Vol
0 to 660 V
Pole Characteristics Maximum Power Rating At Single Phase 120 Vo
2 hp
Pole Characteristics Maximum Power Rating At Single Phase 230 Vo
3 hp
Pole Characteristics Maximum Power Rating At Three Phase 200 Vol
5 hp
Pole Characteristics Maximum Power Rating At Three Phase 230 Vol
7.5 hp
Pole Characteristics Maximum Power Rating At Three Phase 480 Vol
15 hp
Pole Characteristics Maximum Power Rating At Three Phase 600 Vol
20 hp
Pole Characteristics Number Of Power Poles
3
Pole Characteristics Power Dissipation Per Pole For Ac 3 The Abo
0.8 W
Pole Characteristics Rated Breaking Capacity 650 To 690 Volt V V
120 A
Pole Characteristics Rated Breaking Capacity At 500 Voltage V
250 A
Pole Characteristics Rated Insulation Voltage
1000 V