The 32 Amp T-Range 3 Pole Mechanically Interlocked Contactors with AC Operating Coil (Pre-wired) from Shamrock Controls offer a maximum inductive alternating current of 22A and operational efficiency for various voltage ranges. With approvals from CSA and UL, these contactors adhere to multiple industry standards like BSEN60947, IEC60947, and more. The product features normally closed/open auxiliary contacts, a protective treatment of TH, and conforms to VDE 0106 protection standards.
Product Specifications
Control Circuit Characteristics Average Consumption At 20 Degree
0.3 V·A
Control Circuit Characteristics Average Operating Time At Rated
4 to 12 ms
Control Circuit Characteristics Mechanical Life Rated Control Ci
15 cycles
Control Circuit Characteristics Operational Control Voltage For
0.8 to 1.1 Uc
Control Circuit Characteristics Rated Control Circuit Voltage Uc
12 to 660 V
Control Circuit Characteristics Rated Operational Voltage
0 to 660 V
Dimensions Depth D
85 mm
Dimensions Dimension C
85 mm
Dimensions Dimension D Lacdk1
138 mm
Dimensions Dimension D Ta1
118 mm
Dimensions Dimension D Ta2ta3
125 mm
Dimensions Dimension G
35 mm
Dimensions Height H
74 mm
Dimensions Minimum Electrical Clearance D
10 mm
Dimensions Width W
45 mm
Pole Characteristics Maximum Power Rating At Three Phase 200 Vol
5 hp
Pole Characteristics Maximum Power Rating At Three Phase 230 Vol
5 hp
Pole Characteristics Maximum Power Rating At Three Phase 480 Vol
10 hp
Pole Characteristics Maximum Power Rating At Three Phase 600 Vol
15 hp
Pole Characteristics Number Of Power Poles
3
Pole Characteristics Power Dissipation Per Pole For Ac 3 The Abo
0.8 W
Pole Characteristics Rated Breaking Capacity 220 To 440 Volt V
300 A
Pole Characteristics Rated Breaking Capacity 650 To 690 Volt V V
120 A
Pole Characteristics Rated Breaking Capacity At 500 Voltage V
250 A
Pole Characteristics Rated Insulation Voltage
1000 V
Pole Characteristics Rated Making Capacity Conforming To Interna
300 A