38A Maximum Inductive AC T-Range 3 Pole Contactor
38A Maximum Inductive AC T-Range 3 Pole Contactor
SKU:DPC-c9d4f3
Reliable 38A Inductive 3 Pole AC Contactor with Safety Approvals & Enhanced Efficiency
Regular price
$279.99
Regular price
Sale price
$279.99
Unit price
per
Delivery via Maden
Expect your order to arrive on time.
Secure Payments
All orders are processed through a secure, PCI-compliant checkout.





The 38A Maximum Inductive AC T-Range 3 Pole Mechanically Interlocked Contactor by Shamrock Controls is a robust and reliable solution designed for applications requiring up to 20hp at 480V. With a range of approvals including CSA and UL, this contactor ensures safety and performance. It features normally closed and normally open auxiliary contacts, conforming to various international standards such as BSEN60947 and IEC60947. Suitable for a wide frequency range of 25 to 400 Hz, this contactor offers durability and efficiency in demanding operational environments.
Product Specifications
Control Circuit Characteristics Average Consumption At 20 Degree
0.3 V·A
Control Circuit Characteristics Average Operating Time At Rated
5 to 19 ms
Control Circuit Characteristics Mechanical Life Rated Control Ci
12 cycles
Control Circuit Characteristics Operational Control Voltage For
0.8 to 1.1 Uc
Control Circuit Characteristics Rated Control Circuit Voltage Uc
12 to 660 V
Control Circuit Characteristics Rated Operational Voltage
0 to 660 V
Dimensions Depth D
99 mm
Dimensions Dimension C
98 mm
Dimensions Dimension D Lacdk1
152 mm
Dimensions Dimension D Ta1
131 mm
Dimensions Dimension D Ta2ta3
140 mm
Dimensions Dimension G
44 mm
Dimensions Height H
84 mm
Dimensions Minimum Electrical Clearance D
10 mm
Dimensions Width W
56 mm
Pole Characteristics Maximum Power Rating At Three Phase 200 Vol
10 hp
Pole Characteristics Maximum Power Rating At Three Phase 230 Vol
10 hp
Pole Characteristics Maximum Power Rating At Three Phase 480 Vol
20 hp
Pole Characteristics Maximum Power Rating At Three Phase 600 Vol
25 hp
Pole Characteristics Number Of Power Poles
3
Pole Characteristics Power Dissipation Per Pole For Ac 3 The Abo
2 W
Pole Characteristics Rated Breaking Capacity 220 To 440 Volt V
550 A
Pole Characteristics Rated Breaking Capacity 650 To 690 Volt V V
180 A
Pole Characteristics Rated Breaking Capacity At 500 Voltage V
450 A
Pole Characteristics Rated Insulation Voltage
1000 V
Pole Characteristics Rated Making Capacity Conforming To Interna
550 A