The 65A Setting Overload Relay by Shamrock Controls is a reliable Class 10 relay with a rated tripping class of 10, designed for overload protection with a setting range of 48 to 65 Amps. This durable relay offers a power range of 18.5 kW to 50 kW across various voltage settings, conforming to international standards such as BSEN60947, IEC60947-1, and IEC60947-4-1. With approvals from CSA, IEC, and UL, this relay ensures optimal protection and performance in a wide range of applications.
Product Specifications
Auxiliary Contact Charactericstics Coil Of Controlled Contactors
600 V·A
Auxiliary Contact Charactericstics Conventional Thermal Current
5 A
Auxiliary Contact Charactericstics Flexible Cable Without Cable
1/2.5 mm²
Auxiliary Contact Charactericstics Flexible Cable With Cable End
1/2.5 mm²
Auxiliary Contact Charactericstics Maximum Consumption Of Operat
220 V | 380 V
Auxiliary Contact Charactericstics Short Circuit Protection Powe
25 W | 45 W
Auxiliary Contact Charactericstics Solid Cable Without Cable End
1/2.5 mm²
Auxiliary Contact Charactericstics Tightening Torque 1 Or 2 Cond
1.85 N·m
Electrical Charactericstics Of Power Circuit Connecting To Screw
Maximum Canadian Standards Association (CSA) | Minimum Canadian Standards Association (CSA)
Electrical Charactericstics Of Power Circuit Connection To Sprin
Maximum Canadian Standards Association (CSA) | Minimum Canadian Standards Association (CSA)
Electrical Charactericstics Of Power Circuit Depending On Model
17 to 70 A
Electrical Charactericstics Of Power Circuit Flexible Cable With
4/35 mm²
Electrical Charactericstics Of Power Circuit Frequency Limits Of
0 to 400 Hz
Electrical Charactericstics Of Power Circuit Rated Impulse Withs
6 kV
Electrical Charactericstics Of Power Circuit Rated Insulation Vo
1000 V
Electrical Charactericstics Of Power Circuit Rated Operating Vol
600 V
Electrical Charactericstics Of Power Circuit Solid Cable Without
4/35 mm²
Electrical Charactericstics Of Power Circuit Tightening Torque 1
9 N·m
Electrical Charactericstics Of Power Circuit Tripping Class
10
Environment Ambient Air Operating Without Derating Temperature A
-25 to 60 ºC
Environment Ambient Air Storage Temperature Around The Device
-60 to 70 ºC
Environment Approvals
Canadian Standards Association (CSA) | International Electrotechnical Commission (IEC) | Underwriters' Laboratories (UL)
Environment Conforming To Standards
BSEN60947 | IEC60947-1 | IEC60947-4-1 | NFCEN 60947-4-1 | VDE0660
Environment Degree Of Protection Conforming To Vde 0106
Protection Against Direct Finger Contact Ingress Protection (IP2X)
Environment Dielectric Strength At 50 Hertz Hz Frequency Conform
6 kV
Environment Impulse Withstand Voltage Conforming To Internationa
6 kV
Environment Maximum Ambient Air Operating Temperature Around The
70 ºC
Environment Minimum Ambient Air Operating Temperature Around The
-40 ºC
Environment Permissible Acceleration Shock Resistance Conforming
11 ms | 15 g
Environment Protective Treatment Conforming To International Ele
TH
Note Note
Protected shrouds for main poles or power poles to be ordered separately for LR1 RelaysUnder Underwriters' Laboratories (UL)/Canadian Standards Association (CSA) Approval
Specifications Back Up Fuse Rating Em
63 A
Specifications Power At 220 Volt V
18.5 kW
Specifications Power At 380 Volt V
25 kW
Specifications Power At 415 Volt V
30 kW
Specifications Power At 440 Volt V
30 kW
Specifications Power At 660 Volt V
50 kW