80-125A 3-Pole T-Range AC Contactors with Pre-Wired Operating Coil
80-125A 3-Pole T-Range AC Contactors with Pre-Wired Operating Coil
SKU:DPC-905494
High-quality 80-125A 3-Pole AC Contactors with Pre-wired Coil, ensuring reliable performance and safety.
Regular price
$299.99
Regular price
Sale price
$299.99
Unit price
per
Delivery via Maden
Expect your order to arrive on time.
Secure Payments
All orders are processed through a secure, PCI-compliant checkout.





The 80-125 Ampere Alternating Current T-Range 3 Pole Mechanically Interlocked Contactors by Shamrock Controls are designed for maximum inductive AC current up to 50A. With a range of power ratings and auxiliary contacts, this contactor meets various international standards and approvals, ensuring reliable performance and safety. Suitable for a wide range of applications, these contactors offer high-quality control circuit characteristics and dimensions for efficient operation.
Product Specifications
Control Circuit Characteristics Average Consumption At 20 Degree
0.3 V·A
Control Circuit Characteristics Average Operating Time At Rated
8 to 12 ms
Control Circuit Characteristics Mechanical Life Rated Control Ci
6 cycles
Control Circuit Characteristics Operational Control Voltage For
0.8 to 1.1 Uc
Control Circuit Characteristics Rated Control Circuit Voltage Uc
12 to 660 V
Control Circuit Characteristics Rated Operational Voltage
0 to 660 V
Dimensions Depth D
114 mm
Dimensions Dimension C
114 mm
Dimensions Dimension D 008
124 mm
Dimensions Dimension D Lacdk1
166 mm
Dimensions Dimension D Ta1
145 mm
Dimensions Dimension G
40 mm
Dimensions Height H
127 mm
Dimensions Minimum Electrical Clearance D
12 mm
Dimensions Width W
75 mm
Pole Characteristics Maximum Power Rating At Three Phase 200 Vol
15 hp
Pole Characteristics Maximum Power Rating At Three Phase 230 Vol
15 hp
Pole Characteristics Maximum Power Rating At Three Phase 480 Vol
40 hp
Pole Characteristics Maximum Power Rating At Three Phase 600 Vol
40 hp
Pole Characteristics Number Of Power Poles
3
Pole Characteristics Power Dissipation Per Pole For Ac 3 The Abo
3.7 W
Pole Characteristics Rated Breaking Capacity 220 To 440 Volt V
900 A
Pole Characteristics Rated Breaking Capacity 650 To 690 Volt V V
500 A
Pole Characteristics Rated Breaking Capacity At 500 Voltage V
900 A
Pole Characteristics Rated Insulation Voltage
1000 V
Pole Characteristics Rated Making Capacity Conforming To Interna
900 A