The 9 Amp Maximum Inductive Alternating Current (AC) T-Range 3 Pole Mechanically Interlock Contactor offers reliable control for AC circuits. With a maximum resistive AC capacity of 25 A and various power ratings, this compact contactor conforms to several international standards including BSEN60947, IEC60947, and UL approvals. Suitable for DP contactors, it ensures efficient operation within a wide range of environmental conditions.
Product Specifications
Control Circuit Characteristics Average Consumption At 20 Degree
0.3 V·A
Control Circuit Characteristics Average Operating Time At Rated
4 to 12 ms
Control Circuit Characteristics Mechanical Life Rated Control Ci
15 cycles
Control Circuit Characteristics Operational Control Voltage For
0.8 to 1.1 Uc
Control Circuit Characteristics Rated Control Circuit Voltage Uc
12 to 660 V
Control Circuit Characteristics Rated Operational Voltage
0 to 660 V
Dimensions Depth D
80 mm
Dimensions Dimension C
80 mm
Dimensions Dimension D Lacdk1
133 mm
Dimensions Dimension D Ta1
113 mm
Dimensions Dimension D Ta2ta3
120 mm
Dimensions Dimension G
35 mm
Dimensions Height H
74 mm
Dimensions Minimum Electrical Clearance D
10 mm
Dimensions Width W
45 mm
Pole Characteristics Maximum Power Rating At Three Phase 200 Vol
2 hp
Pole Characteristics Maximum Power Rating At Three Phase 230 Vol
2 hp
Pole Characteristics Maximum Power Rating At Three Phase 480 Vol
5 hp
Pole Characteristics Maximum Power Rating At Three Phase 600 Vol
7.5 hp
Pole Characteristics Number Of Power Poles
3
Pole Characteristics Power Dissipation Per Pole For Ac 3 The Abo
0.2 W
Pole Characteristics Rated Breaking Capacity 220 To 440 Volt V
250 A
Pole Characteristics Rated Breaking Capacity 650 To 690 Volt V V
85 A
Pole Characteristics Rated Breaking Capacity At 500 Voltage V
175 A
Pole Characteristics Rated Insulation Voltage
1000 V
Pole Characteristics Rated Making Capacity Conforming To Interna
250 A