National Compressor Exchange, Inc. →

Copeland Reciprocating Tandem Compressors

Copeland Reciprocating Tandem Compressors

SKU:COM-997700

High-performance Copeland Reciprocating Tandem Compressors for industrial and commercial applications. CFH 4760, 20 HP, Net Weight 930 lbs, oil charge 540 oz.

Regular price $3,500.00
Regular price Sale price $3,500.00
Sale

Initiate Order

Copeland Reciprocating Tandem Compressors

Copeland Reciprocating Tandem Compressors

$3,500.00

Quantity: 1

Claim Your Seller Account

Copeland Reciprocating Tandem Compressors

Copeland Reciprocating Tandem Compressors

$3,500.00

Quantity: 1

Delivery via Maden

Expect your order to arrive on time.

Secure Payments

All orders are processed through a secure, PCI-compliant checkout.

View full details
The Copeland Reciprocating Tandem Compressors, including Models 44D, 44R, 66D, and 66R, are reliable and high-performance compressors designed for industrial and commercial applications. With a net weight of 930 lbs and a nominal HP of 20, these compressors provide a CFH of 4760 at 60 Hz. They come with a Catalog Number CPE-90T and consist of two 4DA*1000 models. The compressors are equipped with oil charges totaling 540 oz, ensuring smooth and efficient operation. Additionally, they include various accessories such as pumps, crankcase heaters, unloaders, valve plates, and gaskets for enhanced functionality.

Product Specifications

Accessories Accessories
CPE-1006-P, Pumps | CPE-1022-H, Crankcase Heaters | CPE-1024-H, Crankcase Heaters | CPE-1034-E, Accessories | CPE-1055-U, Unloaders | CPE-1056-E, Accessories | CPE-1087-T, Terminal Plates & Parts | CPE-1088-T, Terminal Plates & Parts | CPE-1118-VP, Valve Plates & Parts | CPE-1119-VP, Valve Plates & Parts | CPE-1133-GK-F, Gaskets | NCE-1002-E, Accessories | NCE-1003-E, Accessories | NCE-1004-E, Accessories | NCE-1007-E or CPE-1007-E, Accessories | NCE-1010-E, Accessories
Evacuation Procedure 0
System Cleanliness System cleanliness is one of the most important factors that affect system and compressor reliability. System contamination can cause both mechanical and electrical failures. There are several sources ofsystem contamination. Some of these are: Copper oxides from system refrigerant piping brazing. Refrigerant piping chips and burrs and brazing flux. Processing residue and metal chips from evaporators and condensers. Metal chips and wire brush strands from processing of other system components. Contamination in refrigeration tubing which is left uncapped during assembly. Moisture and air. In addition, field erected systems are subject to all the dirt and system contamination of the typical jobsite. It is recommended that a suction line filter be installed in the system to prevent contaminants form entering the compressor ; Evacuation and Dehydration For the refrigeration system to work property, it must be free of air and moisture. The process by which air and moisture are removed is known as evacuation and dehydration. Moisture and air are harmful to the system because they increase the condensing temperature, raise the discharge gas temperature, cause oil breakdown and the formation of acids. Acids are corrosive to the components in the refrigeration system, including the piping, refrigerant specialties, and the which can cause mechanical failure of the compressor.The recommended method for evacuation and dehydration is to evacuate the system from both the gigh and low sides to 800 microns or less. To establish that the unit is leakfree and moisture-free, a standing vacuum test is recommended. The maximum allowable rise over a 15 minute period is 200 microns. If the Hse exceeds this, either there is still moisture in teh system or a leak is present in the system See Chart 1.CAUTIONNEVER USE OXYGEN OR ACETYLENE IN PLACE OF REFRIGERANT AND DRY NITROGEN FOR LEAK TESTING. A VIOLENT EXPLOSION MAY RESULT, CAUSING PERSONAL INJURY OR DEATH.ALWAYS USE A PRESSURE REGULATOR WHEN USING NITROGEN TO PRESSURE TEST. FAILURE TO DO SO WILL RESULT IN EXTREMELY HIGH PRESSURE WHICH COULD EXCEED THE BURST PRESSURE OF TEH COMPRESSOR OR OTHER SYSTEM COMPONENTS AND RESULT IN PERSONAL INJURY OR DEATH.FOR SHELF STORAGE EVAC. TO 250 MICRONS
Notes Note
No. 1 or No. 2 preceeding model A or B indicates R-12 or R-22. Rebuilt compressors are interchangeable.R after model number indicates right hand compressors on Tandem unit unloader control and oil equalizer lines on the reverse side. This is the only difference. A-Letter may be B-C-D-E, which is design sequence.
Specifications Catalog Number
CPE-90T
Specifications Cfh 60 Hz
4760
Specifications Consisting Of Two Models
4DA*1000
Specifications Model
Line Tandem
Specifications Net Weight Lbs
930
Specifications Nominal Hp
20
Specifications Oil Charge Oz
280, 260
Specifications Ship Weight Lbs
1000