Inductive AC T-Range 3 Pole Mechanically Interlocked Contactor
Inductive AC T-Range 3 Pole Mechanically Interlocked Contactor
SKU:DPC-8bb50e
Reliable 18A AC T-Range Contactor for industrial and institutional use, meets BSEN60947, IEC60947, UL, CSA standards.
Regular price
$129.99
Regular price
Sale price
$129.99
Unit price
per
Delivery via Maden
Expect your order to arrive on time.
Secure Payments
All orders are processed through a secure, PCI-compliant checkout.





The 18 Ampere Maximum Inductive AC T-Range 3 Pole Mechanically Interlocked Contactor by Shamrock Controls is a reliable solution for industrial and institutional applications. With a wide range of power ratings, auxiliary contact types, and impressive durability, this contactor meets stringent industry standards including BSEN60947, IEC60947, UL, CSA, and more. Ensure seamless operation and compliance with the highest quality standards with this contactor.
Product Specifications
Control Circuit Characteristics Average Consumption At 20 Degree
0.3 V·A
Control Circuit Characteristics Average Operating Time At Rated
4 to 12 ms
Control Circuit Characteristics Mechanical Life Rated Control Ci
15 cycles
Control Circuit Characteristics Operational Control Voltage For
0.8 to 1.1 Uc
Control Circuit Characteristics Rated Control Circuit Voltage Uc
12 to 660 V
Control Circuit Characteristics Rated Operational Voltage
0 to 660 V
Dimensions Depth D
85 mm
Dimensions Dimension C
85 mm
Dimensions Dimension D Lacdk1
138 mm
Dimensions Dimension D Ta1
118 mm
Dimensions Dimension D Ta2ta3
125 mm
Dimensions Dimension G
35 mm
Dimensions Height H
74 mm
Dimensions Minimum Electrical Clearance D
10 mm
Dimensions Width W
45 mm
Pole Characteristics Maximum Power Rating At Three Phase 200 Vol
5 hp
Pole Characteristics Maximum Power Rating At Three Phase 230 Vol
5 hp
Pole Characteristics Maximum Power Rating At Three Phase 480 Vol
10 hp
Pole Characteristics Maximum Power Rating At Three Phase 600 Vol
15 hp
Pole Characteristics Number Of Power Poles
3
Pole Characteristics Power Dissipation Per Pole For Ac 3 The Abo
0.8 W
Pole Characteristics Rated Breaking Capacity 220 To 440 Volt V
300 A
Pole Characteristics Rated Breaking Capacity 650 To 690 Volt V V
120 A
Pole Characteristics Rated Breaking Capacity At 500 Voltage V
250 A
Pole Characteristics Rated Insulation Voltage
1000 V
Pole Characteristics Rated Making Capacity Conforming To Interna
300 A