The Shamrock Controls 12 Ampere Maximum Inductive AC T-Range 3 Pole Mechanically Interlock Contactor is designed for reliable performance in industrial settings. With a maximum resistive current of 25A, it offers robust power handling capabilities for critical applications. This product meets stringent industry standards such as BSEN60947 and IEC60947, ensuring compliance and quality. With approvals from CSA and UL, this contactor provides a high degree of protection and reliable operation, making it an ideal choice for both consumer and institutional buyers.
Product Specifications
Control Circuit Characteristics Average Consumption At 20 Degree
0.3 V·A
Control Circuit Characteristics Average Operating Time At Rated
4 to 12 ms
Control Circuit Characteristics Mechanical Life Rated Control Ci
15 cycles
Control Circuit Characteristics Operational Control Voltage For
0.8 to 1.1 Uc
Control Circuit Characteristics Rated Control Circuit Voltage Uc
12 to 660 V
Control Circuit Characteristics Rated Operational Voltage
0 to 660 V
Dimensions Depth D
80 mm
Dimensions Dimension C
80 mm
Dimensions Dimension D Lacdk1
133 mm
Dimensions Dimension D Ta1
113 mm
Dimensions Dimension D Ta2ta3
120 mm
Dimensions Dimension G
35 mm
Dimensions Height H
74 mm
Dimensions Minimum Electrical Clearance D
10 mm
Dimensions Width W
45 mm
Pole Characteristics Maximum Power Rating At Three Phase 200 Vol
3 hp
Pole Characteristics Maximum Power Rating At Three Phase 230 Vol
3 hp
Pole Characteristics Maximum Power Rating At Three Phase 480 Vol
7.5 hp
Pole Characteristics Maximum Power Rating At Three Phase 600 Vol
10 hp
Pole Characteristics Number Of Power Poles
3
Pole Characteristics Power Dissipation Per Pole For Ac 3 The Abo
0.36 W
Pole Characteristics Rated Breaking Capacity 220 To 440 Volt V
250 A
Pole Characteristics Rated Breaking Capacity 650 To 690 Volt V V
85 A
Pole Characteristics Rated Breaking Capacity At 500 Voltage V
175 A
Pole Characteristics Rated Insulation Voltage
1000 V
Pole Characteristics Rated Making Capacity Conforming To Interna
250 A