Skip to product information
1 of 3
Shamrock Controls div. of Burns Controls Company →

Shamrock Controls 3-Pole Definite Purpose Contactor - 60Hz Frequency

Shamrock Controls 3-Pole Definite Purpose Contactor - 60Hz Frequency

SKU:DPC-a642ad

Reliable 3-Pole Definite Purpose Contactor by Shamrock Controls, perfect for motors, power supplies, HVAC, and more

Regular price $59.99
Regular price Sale price $59.99
Sale

Initiate Order

Shamrock Controls 3-Pole Definite Purpose Contactor - 60Hz Frequency

Shamrock Controls 3-Pole Definite Purpose Contactor - 60Hz Frequency

$59.99

Quantity: 1

Claim Your Seller Account

Shamrock Controls 3-Pole Definite Purpose Contactor - 60Hz Frequency

Shamrock Controls 3-Pole Definite Purpose Contactor - 60Hz Frequency

$59.99

Quantity: 1

Delivery via Maden

Expect your order to arrive on time.

Secure Payments

All orders are processed through a secure, PCI-compliant checkout.

View full details
The Shamrock Controls 3-Pole Definite Purpose Contactor is designed for precise control of motors, power supplies, heating elements, lighting, HVAC fans, and compressors. With a robust construction and a coil voltage of 120V at 60Hz frequency, this contactor ensures reliable performance in demanding environments. It offers a Full Load Expected Life of 200,000 cycles, making it ideal for industrial applications requiring durability and efficiency.

Product Specifications

Coil Data Coil Voltage
120
Coil Data Duty Cycle
Continuous
Coil Data Frequency
60 Hz
Coil Data Minimum Initial Insulation Resistance
100 MΩ
Coil Data Normal Inrush Apparent Power
65 V·A
Coil Data Sealed Apparent Power
7.5 V·A
Environment Ambient Air Dampness Around The Device Relative Humi
45 to 85 %
Environment Ambient Air Temperature
40 to 65 ºC
Environment Coil Apply Voltage At 60 Hertz Hz Frequency
80 to 110 %
Environment Maximum Operating Altitude Above Sea Level
2000 m
Environment Operating Temperature
-5 to 55 ºC
Specifications Number Of Poles
3
Technical Data Full Load Expected Life
200000
Technical Data Full Load Inductive Current
30 A
Technical Data Locked Rotor Per Pole Current At 240 Alternating
180 A
Technical Data Locked Rotor Per Pole Current At 480 Alternating
150 A
Technical Data Locked Rotor Per Pole Current At 600 Alternating
120 A
Technical Data Mechanical Alternating Current Ac Coil Operations
2 Million
Technical Data Minimum Contact Data At 120 Alternating Current V
3 A
Technical Data Resistive Rating Current
40 A